                                  This is the web edition of the original ⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.  | 
                           
The errors are shown as they are displayed in Automation Builder. In AC500-S Programming Tool, errors are displayed similar to error messages of AC500 V2 non-safety CPUs.
| 
                                  Severity  | 
                              
                                  Error code  | 
                              
                                  Description  | 
                              
                                  Remedy  | 
                           
|---|---|---|---|
| 
                                  2  | 
                              
                                  8235  | 
                              
                                  Internal error  | 
                              
                                  Replace module  | 
                           
| 
                                  2  | 
                              
                                  8448  | 
                              
                                  Operation finished  | 
                              
                                  Change Safety PLC switch address setting or remove SD-Card from non-safety PLC. Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8449  | 
                              
                                  Wrong user data  | 
                              
                                  Delete user data from Safety PLC. Restart Safety PLC and write user data again.  | 
                           
| 
                                  2  | 
                              
                                  8450  | 
                              
                                  Internal PROFIsafe initialization error  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support.  | 
                           
| 
                                  2  | 
                              
                                  8460  | 
                              
                                  Flash read error  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support.  | 
                           
| 
                                  2  | 
                              
                                  8466  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8476  | 
                              
                                  Boot project download error  | 
                              
                                  Reload boot project. If this error persists, replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8488  | 
                              
                                  Wrong firmware version  | 
                              
                                  Update Safety PLC firmware. Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8491  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8496  | 
                              
                                  Overvoltage or undervoltage detected  | 
                              
                                  Restart Safety PLC. Check Safety PLC setting for power supply error. If this error persists, replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8500  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8704  | 
                              
                                  User program triggered safe stop  | 
                              
                                  Check user program  | 
                           
| 
                                  2  | 
                              
                                  8705  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8706  | 
                              
                                  Internal PROFIsafe error  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support.  | 
                           
| 
                                  2  | 
                              
                                  8707  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8714  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8717  | 
                              
                                  Flash write error  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support.  | 
                           
| 
                                  2  | 
                              
                                  8721  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8722  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8723  | 
                              
                                  Checksum error has occured in Safety PLC  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8729  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8741  | 
                              
                                  Cycle time error in Safety PLC  | 
                              
                                  Check Safety PLC watchdog time.  | 
                           
| 
                                  2  | 
                              
                                  8742  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8746  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8747  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8756  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8758  | 
                              
                                  Internal error  | 
                              
                                  Contact ABB technical support. Replace Safety PLC.  | 
                           
| 
                                  2  | 
                              
                                  8990  | 
                              
                                  PROFIsafe configuration error  | 
                              
                                  Check F-Parameter configuration of I/O module and reload boot project  | 
                           
| 
                                  3  | 
                              
                                  12561  | 
                              
                                  Safety source addresses cannot be checked  | 
                              
                                  Check PROFIsafe F-Host library version (2.0.0 or above). If this error persists, contact ABB technical support.  | 
                           
| 
                                  3  | 
                              
                                  12570  | 
                              
                                  Error in configuration data, safety PLC has not accepted configuration data, e.g., mismatch between safety and non-safety PLC configuration.  | 
                              
                                  Create new configuration data for both safety and non-safety PLC again, re-create and download boot projects to both safety and non-safety PLC again.  | 
                           
| 
                                  3  | 
                              
                                  12571  | 
                              
                                  Error in configuration data, Safety PLC cannot read configuration data  | 
                              
                                  Create boot project  | 
                           
| 
                                  3  | 
                              
                                  12598  | 
                              
                                  PROFIsafe F_Dest_Add rules are violated  | 
                              
                                  Check Safety PLC configuration or switch address setting against PROFIsafe F_Dest_Add configuration rules. Restart Safety PLC. If this error persists, contact ABB technical support.  | 
                           
| 
                                  3  | 
                              
                                  32770  | 
                              
                                  Watchdog error coupler  | 
                              |
| 
                                  3  | 
                              
                                  32771  | 
                              
                                  Wrong firmware version of Communication Module  | 
                              
                                  Update firmware  | 
                           
| 
                                  3  | 
                              
                                  32772  | 
                              
                                  Initialisation of Safety Module on slot failed. More than one Safety Module plugged  | 
                              
                                  Remove this module or Only that one Safety Module plugged -> defective, replace this module  | 
                           
| 
                                  3  | 
                              
                                  32774  | 
                              
                                  Invalid configuration data  | 
                              
                                  Check configuration  | 
                           
| 
                                  3  | 
                              
                                  32775  | 
                              
                                  Safety Module not found  | 
                              
                                  Check configuration. At Safety PLC: Check Safety PLC switch address setting. Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  3  | 
                              
                                  32776  | 
                              
                                  Safety Module has wrong type  | 
                              
                                  Check configuration  | 
                           
| 
                                  3  | 
                              
                                  32777  | 
                              
                                  Program not started because of configuration error  | 
                              
                                  Check configuration  | 
                           
| 
                                  3  | 
                              
                                  32778  | 
                              
                                  Program not started, no application running in Safety Module  | 
                              
                                  Check configuration, download safety application to Safety Module  | 
                           
| 
                                  4  | 
                              
                                  16640  | 
                              
                                  Reserved switch address setting.  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  16644  | 
                              
                                  Boot project not loaded, maximum power dip reached  | 
                              
                                  Restart Safety PLC  | 
                           
| 
                                  4  | 
                              
                                  16648  | 
                              
                                  Power dip data missed or corrupted. Default power dip data was flashed by Safety PLC  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  16659  | 
                              
                                  CRC error boot project  | 
                              
                                  Create new boot project and restart Safety PLC  | 
                           
| 
                                  4  | 
                              
                                  16909  | 
                              
                                  Flash write error (production data)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  16935  | 
                              
                                  More than one instance of SF_WDOG_TIME_SET or SF_MAX_POWER_DIP_SET  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  16922  | 
                              
                                  No or wrong configuration data from PM5x, run state not possible  | 
                              
                                  Create correct boot project at PM5x  | 
                           
| 
                                  4  | 
                              
                                  17421  | 
                              
                                  Flash write error (boot project)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  17677  | 
                              
                                  Flash write error (boot code)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  17933  | 
                              
                                  Flash write error (firmware)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  18189  | 
                              
                                  Flash write error (password)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  18445  | 
                              
                                  Flash write error (user data)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  18701  | 
                              
                                  Flash write error (user data)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  18957  | 
                              
                                  Flash write error (internal)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  19213  | 
                              
                                  Flash write error (internal)  | 
                              
                                  Warning  | 
                           
| 
                                  4  | 
                              
                                  19469  | 
                              
                                  Flash write error (internal)  | 
                              
                                  Warning  | 
                           
| 
                                  Severity  | 
                              
                                  SubSysteminfo <n>  | 
                              
                                  Error code  | 
                              
                                  Description  | 
                              
                                  Remedy  | 
                           
|---|---|---|---|---|
| 
                                  2  | 
                              
                                  0 - 31  | 
                              
                                  28715  | 
                              
                                  F-device instance <n>, Internal PROFIsafe error  | 
                              
                                  Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28673  | 
                              
                                  F-device instance <n>, Safety destination address not valid (F_Dest_Add)  | 
                              
                                  Check Safety PLC configuration or switch address setting. Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28674  | 
                              
                                  F-device instance <n>, Safety source address not valid (F_Source_Add)  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28682  | 
                              
                                  F-device instance <n>, Parameter "F_SIL" exceeds SIL from specific device application  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28683  | 
                              
                                  F-device instance <n>, Safety watchdog time value is 0 ms (F_WD_Time)  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28691  | 
                              
                                  F-device instance <n>, CRC1-Fault  | 
                              
                                  Check Safety PLC configuration. If this error persists, contact ABB technical support.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28692  | 
                              
                                  F-device instance <n>, PROFIsafe communication error  | 
                              
                                  Restart the module. If this error persists, contact ABB technical support.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28697  | 
                              
                                  F-device instance <n>, PROFIsafe watchdog timed out  | 
                              
                                  Restart the module. If this error persists, increase PROFIsafe watchdog time.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28698  | 
                              
                                  F-device instance <n>, Parameter "F_Block_ID" is invalid  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28700  | 
                              
                                  F-device instance <n>, Mismatch of safety destination address (F_Dest_Add)  | 
                              
                                  Check Safety PLC configuration or switch address setting. Restart Safety PLC. If this error persists, replace Safety PLC.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28712  | 
                              
                                  F-device instance <n>, Version of F-Parameter set incorrect  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  3  | 
                              
                                  0 - 31  | 
                              
                                  28714  | 
                              
                                  F-device instance <n>, Parameter "F_CRC_Length" does not match the generated values  | 
                              
                                  Check Safety PLC configuration.  | 
                           
| 
                                  AC500/AC500-S error code  | 
                              
                                  PROFINET channel error type  | 
                              
                                  PROFINET diagnostic information  | 
                           
|---|---|---|
| 
                                  28700  | 
                              
                                  64  | 
                              
                                  Mismatch of safety destination address (F_Dest_Add)  | 
                           
| 
                                  28673  | 
                              
                                  65  | 
                              
                                  Safety destination address not valid (F_Dest_Add)  | 
                           
| 
                                  28674  | 
                              
                                  66  | 
                              
                                  Safety source address not valid (F_Source_Add)  | 
                           
| 
                                  28683  | 
                              
                                  67  | 
                              
                                  Safety watchdog time value is 0 ms (F_WD_Time)  | 
                           
| 
                                  28682  | 
                              
                                  68  | 
                              
                                  Parameter "F_SIL" exceeds SIL from specific device application  | 
                           
| 
                                  28714  | 
                              
                                  69  | 
                              
                                  Parameter "F_CRC_Length" does not match the generated values  | 
                           
| 
                                  28712  | 
                              
                                  70  | 
                              
                                  Version of F-Parameter set incorrect  | 
                           
| 
                                  28691  | 
                              
                                  71  | 
                              
                                  CRC1-Fault  | 
                           
| 
                                  28698  | 
                              
                                  76  | 
                              
                                  F_Block_ID not supported  | 
                           
| 
                                  28692  | 
                              
                                  77  | 
                              
                                  Transmission error: data inconsistent (CRC2 error)  | 
                           
| 
                                  28697  | 
                              
                                  78  | 
                              
                                  Transmission error: timeout (F_WD_Time or F_WD_Time_2 elapsed)  |