                                  This is the web edition of the original ⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.  | 
                           
The arrangement of the parameter data is performed by your system configuration software Automation Builder. ABB GSDML file for PROFINET devices can be used to configure AI581-S parameters in 3rd party PROFINET F-Host systems.
The parameter setting directly influences the functionality of modules and reachable SIL (IEC 61508), max. SIL (IEC 62061) and PL (ISO 13849-1).
| 
                                  No.  | 
                              
                                  Name  | 
                              
                                  Values  | 
                              
                                  Default  | 
                           
|---|---|---|---|
| 
                                  1  | 
                              
                                  Check supply  | 
                              
                                  "On", "Off"  | 
                              
                                  "On"  | 
                           
| 
                                  2  | 
                              
                                  Configuration  | 
                              
                                  "Not used", "1 channel (0 ... 20 mA)", "1 channel (4 ... 20 mA)", "2 channel (4 ... 20 mA)"  | 
                              
                                  "Not used"  | 
                           
| 
                                  3  | 
                              
                                  Noise rejection  | 
                              
                                  "50 Hz", "60 Hz", "None"  | 
                              
                                  "50 Hz"  | 
                           
| 
                                  4  | 
                              
                                  Tolerance range (used only for "2 channel (4 ... 20 mA)" mode)  | 
                              
                                  "4 %", "5 %", "6 %", "7 %", "8 %", "9 %", "10 %", "11 %", "12 %"  | 
                              
                                  "4 %"  | 
                           
| 
                                  5  | 
                              
                                  Used value (min/max) (used only for "2 channel (4 ... 20 mA)" mode)  | 
                              
                                  "Minimum", "Maximum"  | 
                              
                                  "Minimum"  |